DigiTMR S2
EHV Circuit Breaker Analyzer
The Vanguard DIGITMR S2 is an inexpensive, easy to use digital circuit breaker analyzer. The DIGITMR S2 can be operated stand-alone or can be computer-controlled. It can fully analyze a circuit-breaker’s performance by testing the contact time, stroke, velocity, over-travel, and contact wipe. Contact and motion analysis can be performed for all breaker contact operations (Open, Close, Open – Close, Close – Open, and Open – Close – Open). Timing results are recorded and displayed on the 240 x 128 pixels back-lit LCD screen and can also be printed on the built-in 4.5″ wide thermal printer.
Cable | Part Number |
---|---|
[8000-0005] USB Cable [ 6′ (1.83m) ] | 8000-0005 |
[8000-0016] Power + Ground Combination Cable | 8000-0016 |
[8000-0095] Contact Extension Cable [ 30′ (9.14m) ] | 8000-0095 |
[8000-0096] Contact Test Lead [ 20′ (6.10m) ] | 8000-0096 |
[8000-0097] Contact Extension Cable [ 30′ (9.14m) ] | 8000-0097 |
[8000-0099] Initiate Cable [ 22′ (6.71m) ] | 8000-0099 |
[8000-0101] Test Lead (Trigger, V1, V2) [ 2′ (0.61m) ] | 8000-0101 |
[8000-0104] Transducer Cable [ 25′ (7.62m) ] | 8000-0104 |
TYPE | portable digital circuit breaker analyzer |
PHYSICAL SPECIFICATIONS | 18.5”W x 14”H x 7”D (47.0 cm x 35.7 cm x 17.6 cm); Weight: 20 lbs (9.1 kg) |
INPUT POWER | 3 Amps, 100 – 240 Vac, 50/60 Hz |
DRY-CONTACT INPUTS | 3 dry-contact channels; each channel detects main contact and insertion resistor contact |
TIMING WINDOWS | 1-second, 10-seconds, or 20-seconds |
TIMING RESOLUTIONS | ±50 micro-seconds @ 1-second duration, ±500 micro-seconds @ 10-second duration, ±1.00 milli-second @ 20-second duration |
TIMING ACCURACY | 0.05% of reading ±0.1 ms @ 1-second duration |
CONTACT DETECTION RANGE | Closed: less than 20 ohms; Open: greater than 5,000 ohm |
RESISTOR DETECTION RANGE | 50 – 5,000 ohms |
TRIGGER INPUT VOLTAGE | Open/Close: 30 – 300V, DC or peak AC |
VOLTAGE SENSING INPUT RANGE | V1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC |
BREAKER OPERATIONS | Initiate Open, Close, Open – Close, Close – Open, Open – Close – Open |
BREAKER INITIATE CAPACITY | 30A, 250 Vac/dc max |
INITIATE CURRENT READING RANGE | One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz |
TRAVEL TRANSDUCER INPUT | 1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.); Rotary range: 0 – 360 degrees (±0.006 degrees) |
CONTACT TRAVEL POINT DIFFERENCE | Measures “slow-close” contact-point distances; results can be printed |
CT CURRENT SENSOR | One, non-contact, 0 – 100A |
DISPLAY | Back-lit LCD screen (240 x 128 pixels); viewable in bright sunlight and low light levels |
PRINTER | Built-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms and tabulated test results |
INTERNAL TEST RECORD STORAGE | Stores up to 200 test records and 100 test plans |
COMPUTER INTERFACES | One USB port, optional Bluetooth interface |
PC SOFTWARE | Windows®-based Vanguard Circuit Breaker Analysis (VCBA S2) software is included with purchase price. Software updates available at no additional charge. |
SAFETY | Designed to meet UL/IEC 61010 and CAN/CSA C22.2 No. 1010.1-92 standards |
ENVIRONMENT | Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F) |
OPTIONS | Transportation case (available for the DigiTMR S2 and the travel transducers) |
WARRANTY | One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |