ATRT-01B S3
Automatic, single-phase transformer turns ratio testers
The ATRT-01B S3 is Vanguard’s fourth generation, micro-processor based, single phase, automatic transformer turns-ratio tester. The ATRT-01B S3 uses the IEEE C57.12.90 measuring method to determine the transformer turns-ratio. The transformer turns-ratio is determined by precisely measuring the voltages across the unloaded transformer windings. The ATRT-01B S3’s measuring circuitry self adjusts before each measurement to ensure turns-ratio accuracy. Two selectable test voltages, 4Vac and 40Vac, offer flexibility in testing different types of transformers. The ATRT-01B S3 is battery or AC-powered. The unit can be used continuously for up to 4 hours pwer charge and can be used during charging.
Cable | Part Number |
---|---|
[8000-0006] RS-232C Cable [ 6′ (1.83m) ] | 8000-0006 |
[8000-0200] H and X Cable Set with Male Connectors [15’ (4.57m)] | 8000-0200 |
[8000-0112] Power Cable | 8000-0112 |
TYPE | Transformer Turns Ratio Tester |
PHYSICAL SPECIFICATIONS | Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
Weight: 9 lbs. (4.3 Kg) |
INPUT POWER | 90 to 240 Vac, 50/60 Hz
SLA battery delivering up to 4 hours of continuous operation per charge |
MEASURING METHOD | ANSI/IEEE C57.12.90 |
RATIO MEASURING RANGE | 0.8 – 15,000 (5 digit resolution) |
TURNS-RATIO ACCURACY | 40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%) |
4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%) | |
TEST VOLTAGE | 4 Vac @ 300mA, 40 Vac @ 70mA |
PHASE ANGLE MEASUREMENT | 0 – 360 degrees, Accuracy ±0.2 degree (±1 digit) |
POLARITY READING | In-Phase or Out-of-Phase indication |
EXCITATION CURRENT READING RANGE | 0-2 Amperes, Accuracy: 2% of reading (±1 mA) |
DISPLAY | Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
COMPUTER INTERFACE | RS-232C |
PC SOFTWARE | Windows XP/Vista/7 Transformer Analysis Software (included with purchase) |
INTERNAL TEST RECORD STORAGE | 128 records of 33 readings |
EXTERNAL TEST RECORD STORAGE | Up to 999 test records on external USB Flash drive. |
SAFETY | Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards |
ENVIRONMENT | Operating: -10ºC to 50ºC (15ºF to +122ºF) |
Storage: (-30ºC to 70ºC (-22ºF to +158ºF) | |
HUMIDITY (MAX) | 90% RH @ 40˚ C (104˚ F) non-condensing |
ALTITUDE (MAX) | 2000m (6562 ft) to full safety specifications |
CABLES | One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag |
OPTIONS | Transportation Case (Can hold unit and cables) |
WARRANTY | One year on parts and labor |